XX112-36-00 Rev 909 Kollector Hybrid Network Digital Video Recorder Introducing ViconNet 9
UPS System Requirements
Vicon requires the use of Uninterruptible Power Supply (UPS) systems in the electrical power service. Failure
to comply with this will void the unit warranty.
Use the following minimum UPS requirements:
Capacity: 1000 VA/600 W
Maximum operation time:
16 cameras recording/displaying with a typical 15" CRT monitor: 18 minutes
16 cameras recording/displaying with a typical 17" CRT monitor: 5 minutes
Input:
Voltage: 115 VAC/230 VAC
Voltage Range: ±30% (with a 4-step AVR)
Frequency: 47 – 63 Hz (auto detection)
Output:
Voltage: 115 VAC/230 VAC
Voltage Reduction (bat. mode): ±10%
NOTES:
It is required that external devices (such as RAID units, backup drives or external DVD units) be connected to
the power source via UPS when used with the ViconNet system.